Description
Series 61 Low Water Cut Off
Description: The Series PSE-800-M Manual Reset LWCO is a new addition to the McDonnell & Miller probe type low water cut-off group of products. These controls are used as the secondary LWCO on steam boilers and can be used as the primary LWCO on hot water heating boilers.
With a self-cleaning probe, available only on McDonnell & Miller probe type controls, which reduces probe maintenance to once every five years instead of annually. Manual reset models meet requirments of ASME Standard CSD-1.
- For residential and commercial applications
- Electronic Operation
NEW Features and Benefits:
- User-frienly diagnostics
- Red low water and shortened probe LED
- Green power and test LED
- Probe sensitivity: 7,000 ohms
- No lock out with loss of power if probe is in water
- Delay on make (DOM) feature (15 seconds)
- Delay on break (DOB) feature (10 seconds)
- No blow down of control required when mounted directly into boiler tappings
- Test button standard on all models
- Options available include
- Manual reset
- Extended barrel and remote sensor models
- 120 volt and 24 volt models (24 volt models meet ANSI specification Z21.13a
- Power consumption 1.7 VA
- Provisions to add alarm or automatic water feeder
- Maximum ambient temperature 120°F (49°C)
- Maximum steam pressure 15psi (1kg/cm²)
- Maximum water temperature 250°F (121°C)
Electrical Ratings:
Model | Voltage | Motor switch Rating (Amperes) | Pilot Duty | |
Full Load | Locked Rotor | |||
24 VAC | 24 VAC | – | – | 50 VA at 24 VAC |
120 VAC | 120 VAC 240 VAC | 7.5 3.75 | 43.2 21.6 | 125 VA at 120 or 240 VAC 50 or 60 Hz |
Dimensions
Click on the following to view dimensions:
Boiler Controls – MM-825H – Series PSE-800-M Page 31
Ordering Information:
Model Number | Part Number | Description |
PS-801-120 | 153875 | Low water cut-off 120V |
PS-801-M-120 | 153880 | PS-801-120 w/manual reset |
PS-801-U-120 | 153879 | PS-801-120 w/ext. barrel |
PS-801-M-U-120 | 153925 | PS-801-120 w/ext. barrel & manual reset |
PS-802-24 | 153917 | Low water cut-off 24V |
PS-802-M-24 | 153913 | PS-802-24 w/manual reset |
PS-802-U-24 | 153916 | PS-802-24 w/ext. barrel |
PS-802-M-U-24 | 153924 | PS-802-24 w/ext. barrel & manual reset |
PS-802-RX2-24 | 153914 | PS-802-24 w/remote sensor |
Technical Documentation:
Brochure:
MPF 001A PSE-800-M Manual Reset LWCO for Steam Boilers
Installation/Operation Manuals:
MM 284G Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers
MM 289G PSE-800-M Low Water Cut-Off
Catalog Lists:
Boiler Controls – MM-825H – Series PSE-800-M Page 31
Additional information
Weight | 0.5 kg |
---|---|
Title | Default Title |
Reviews
There are no reviews yet.